Cart

CENTECH VIETNAM JSC

Address: No. 91-93, Lane 5, An Phu Ward, District 2, HCM City
Telephone: (+84) 24 6663 2426
Hotline: (+84) 961 739 336
Email: centech@centechvn.com
Operation Time: all weekdays (except Sunday and National Holidays)

Endress+Hauser iTEMP TMT182 Temperature Head Transmitter

Electronic monitoring, conversion and display of input signals - all over the industries.

Free shipping
Credit Card

Overview

Unsurpassed reliability, accuracy and long-term stability in critical processes. The remote configurable transmitter transfers and monitors converted signals from RTD sensors and thermocouples as well as from resistance and voltage signals using selectively HART®, FOUNDATION Fieldbus™-, PROFIBUS® PA-communication. It visualizes the signals on its own backlit display. A field housing allows a direct connection in harsh process areas as well as in hygienic applications as option.


Benefits

  • High reliability in harsh industrial environments due to dual compartment housing and compact, fully potted electronics

  • Backlit display with large measured value, bar graph and status condition indication

  • Diagnostics information according to NAMUR NE107

  • International approvals such as FM, CSA (IS, NI, XP and DIP) and ATEX (Ex ia, Ex nA nL, Ex d and dust ignition-proof); marine approval

  • SIL certification as per IEC 61508:2010

  • Galvanic isolation 2 kV (sensor input / current output)


Application

  • Universal input usable for resistance thermometer (RTD), thermocouple (TC), resistance thermometer (Ω), voltage transmitters (mV)

  • HART ® protocol for converting various input signals to a scalable 4 to 20 mA analog output signal. Operating the transmitter using handheld terminals Field Xpert SFX350/370, field communicator 475 or remotely via PC

  • FOUNDATION Fieldbus™ ITK 6.1.2

  • PROFIBUS® PA Profile 3.02

  • Optional: stainless steel housing for hygienic or Ex d application


Features

Measuring PrincipleResistance Temperature Detector
Input2 x RTD, TC, Ohm, mV
Output4...20 mA HART
FOUNDATION Fieldbus H1
PROFIBUS PA
Auxiliary power supplyHART:
11,5...42 V DC
Ex ia: 11,5...30 V DC
FOUNDATION Fieldbus:
9...32 V DC
Ex ia: 10,5...24 V DC
PROFIBUS PA:
9...32 V DC
Ex ia: 10,5...24 V DC
CommunicationHART-protocol
FOUNDATION Fieldbus
PROFIBUS PA
Installationin field
Accuracy(Pt100, -50...200 °C) <= 0,15 K (HART)
(Pt100, -58...392 °F) <= 0,3 °F (HART)
(Pt100) <= 0,1 K (FF, PA)
(Pt100) <= 0,18 °F (FF, PA)
Galvanic isolationyes
CertificationUL rec. Comp (HART)
FM IS, NI I/1+2/ABCD
CSA IS, NI I/1+2/ABCD
ATEX II1G Ex ia IIC T6
ATEX II2G Ex d IIC T6
ATEX II3G Ex nA IIC T6
ATEX II3G Ex ic IIC T6
ATEX IECEx II2D Ex tb IIIC Db
ATEX II1G Ex ia IIC T6, II2D Ex ia IIIC
FM XP, NI, DIP I,II,III/1+2/A-G
CSA XP, NI, DIP I,II,III/1+2/A-G
FM XP, DIP, IS, NI I,II,III/1+2/A-G
CSA XP, DIP, IS, NI I,II,III/1+2/A-G
FM+CSA XP,DIP, IS, NI I,II,III/1+2/A-G
CSA General Purpose
IECEx Ex d IIC T6 Gb
IECEx Ex ia, Ex d
NEPSI Ex ia IIC T4-T6
NEPSI Ex nA II T4-T6
NEPSI Ex d IIC T4-T6
TIIS Ex ia IIC T4
TIIS Ex ia IIC T6
TIIS Ex d IIC T6
Marine approval only for HART-protocol
SIL2 only for HART-protocol
EAC Ex ia IIC T6 Ga
EAC Ex d IIC T6 Gb


Specification

Data Sheet