Cart

CENTECH VIETNAM JSC

Address: No. 91-93, Lane 5, An Phu Ward, District 2, HCM City
Telephone: (+84) 24 6663 2426
Hotline: (+84) 961 739 336
Email: centech@centechvn.com
Operation Time: all weekdays (except Sunday and National Holidays)

Endress+Hauser iTEMP TMT182 Temperature Head Transmitter

Transformation of sensor signals into stable and standardized output signals for all industries.

Free shipping
Credit Card

Overview

Unsurpassed reliability, accuracy and long-term stability in critical processes over all industries. The configurable transmitter not only transfers converted signals from resistance thermometers (RTD) and thermocouples (TC), it also transfers resistance and voltage signals using HART® communication. It can be installed as an intrinsically safe apparatus in Zone 1 hazardous areas. Swift and easy operation, visualization and maintenance by PC using operating software.


Benefits

  • Front end unit or panel unit operation using the hand operating module or PC

  • High accuracy in total ambient temperature range

  • Fault signal on sensor break or short circuit, NAMUR NE 43 compliant

  • EMC to NAMUR NE 21, CE

  • Ex-Certification: ATEX Ex ia and dust zone 22 in compliance with EN 50281-1; FM IS; CSA IS

  • Galvanic isolation

  • SIL 2 compliant; 
    Marine approval


Application

  • Temperature head transmitter with HART® -protocol for converting various input signals into an scalable 4 to 20 mA analog output signal

  • Input: Resistance thermometer (RTD), thermocouple (TC), Resistance transmitter (Ω), voltage transmitter (mV)

  • HART® -protocol for front end unit or panel unit operation using the hand operating module (DXR275, DXR375) or PC (e. g. ReadWin 2000 or FieldCare)


Features

Measuring PrincipleHead transmitter
Input1 x RTD, TC, Ohm, mV
Output1 x analog 4...20 mA
Auxiliary power supply11,5...35 V DC (standard-version)
11,5...30 V DC (Ex-version)
CommunicationHART-protocol
InstallationTerminal head form B
Accuracy(Pt100, -50...200 °C) <= 0,2 K
(Pt100, -58...392 °F) <= 0,4 °F
Galvanic isolationyes
CertificationUL Ex IS
UL Ex NI
Marine approval
GOST Ex i
FM IS,NI,Class I,Div.1+2,Group ABCD
CSA IS,NI,Class I,Div.1+2,Group ABCD
ATEX II1G Ex ia IIC T4/T5/T6
ATEX II3G Ex nA IIC T4/T5/T6
ATEX II3D
ATEX II1G Ex ia IIC T6, II3D
ATEX II3G Ex nA IIC T6, II3D
FM+CSA IS,NI,Class I,Div.1+2,Group ABCD
CSA General Purpose
IECEx Ex ia IIC T6/T5/T4
ATEX IECEx II1G Ex ia IIC T6 Ga
NEPSI Ex ia IIC T4-T6
NEPSI Ex nA II T4-T6
EAC Ex ia


Specification

Data Sheet